Home » Entire Product Range » Global Water » Global Water FC220 Open Channel Flow Monitor with DC Power
Global Water BJ2000
AVAILABLE IN STOCK
Prices Start From Call for price
Prices shown are for the United Arab Emirates only and are excluding VAT @ 5% Local Rate (Unless Otherwise Stated).
Other countries may incur additional import duties – Please Contact Us for further details and pricing for your location.
Catalog Numbers | Model | Description |
BJ1000 |
FC220-AC | Process controller with AC power Open channel flow sensor not included. Please specify flume/weir type when placing order. |
BJ2000 * | FC220-DC | Process controller with DC Power Open channel flow sensor not included. Please specify flume/weir type when placing order. |
BJ3000 |
FC220-AC-D | Process controller with AC Power w/Datalogger Open channel flow sensor not included. Includes USB datalogger (FR0300 software kit required). Please specify flume/weir type when placing order. |
BJ4000 |
FC220-DC-D | Process controller with DC Power w/Datalogger Open channel flow sensor not included. Includes USB datalogger (FR0300 software kit required). Please specify flume/weir type when placing order. |
Accessories | ||
Catalog Number | Description | |
FR0300 | Global Water Open Channel Flow Monitor Data Logger Software Includes software, manual, and communication cable. Required to use open channel flow monitor data logger. |
|
BH0500 | FCBAT Open Channel Flow Monitor Battery Option Includes Heavy-Duty Weather Resistant Environmental Enclosure and 12V, 4.5Ah rechargable battery. |
Specifications | |
Display/Keypad: | 16 character x 2 line LCD backlit, 8-button tactile keypad |
Capacity: | |
Flow: | 7 digit maximum |
Totalizer: | 9 digit maximum |
Level: | 5 digit maximum Display Resolution: 3 decimal places maximum, Auto-adjusting |
Display Resolution: | 3 decimal places maximum, Auto-adjusting |
Accuracy: | Sensor accuracy + equation/table error + 0.1% + 1 digit |
Units: | |
Level: | Feet, inches, meters, centimeters |
Volume: | Cubic feet, gallons, million gallons, cubic meters, liters |
Time: | Seconds, minutes, hours, days |
Flow: | 20 Combinations of volume and time units above |
Level Sensor Input: | 4-20mA 2-Wire or 3-wire, 0-5VDC, 0-1VDC |
Output: | One 4-20mA scalable, 4 independent SPDT relays (8A @ 250VAC, 5A @ 30VDC resistive) |
Power: | 12VDC or 18-24VDC Input, +/-10% |
Current Draw: | 150mA Maximum, <13mA in Power Saving Mode |
Internal Fuse: | 315mA |
Power Adapter: | 18VDC Universal Power Supply, 90-220VAC Input |
Enclosure: | 7.1×5.1×1.4 inch (18x13x3.5 cm) (WxHxD) |
Weight: | 1 lb (0.45 kg) |
Equation Formats | Manning’s equation for round pipes Manning’s equation for rectangular pipes |
Standard flow equation: | Q=A*(B+Ch)D |
3rd order polynomial: | Q=A+Bh+Ch2+Dh3 |
Pre-defined Tables | |
Parshall: |
1″, 2″, 3″, 6″, 9″, 12″, 24″, 36″, 48″, 60″, 72″ |
Palmer-Bowlus (4D): |
4″, 6″, 8″, 10″, 12″, 15″, 18″, 24″, 30″, 36″ |
H: |
0.4HS, 0.6HS, 0.5H, 0.75H, 1.0H, 1.5H, 2.0H |
Trapezoidal: | 60° |
Weir: | |
V-notch: | 22.5°, 30°, 45°, 60°, 90°, 120° |
Rectangular: | 1′, 2′, 3′ |
Cipolletti: | 1′, 1.5′, 2′, 3′, 4 |
NOTE: Table values are calculated based on specific flow equations. Custom Look-Up Table: One, Factory programmable only, You must provide Global Water with a depth to flow equation or look up table at time of order. Please allow for longer lead times. |
|
AVAILABLE IN STOCK
AVAILABLE IN STOCK
AVAILABLE IN STOCK
AVAILABLE IN STOCK